48V 3000W He Rectifiers 241119.105 Eltek Flatpack2 Rectifier Modules

Products

48V 3000W He Rectifiers 241119.105 Eltek Flatpack2 Rectifier Modules

48V 3000W He Rectifiers 241119.105 Eltek Flatpack2 Rectifier Modules

Flatpack2 48V 3000W HE Rectifiers 241119.105 Eltek Rectifier Modules The original HE rectifier Since setting the new sta

Send your inquiry

DESCRIPTION

Basic Info.
Model NO. 241119.105
Dimensions 109X41.5X327mm
Weight 1.950 Kg [4.3lbs]
Transport Package Plywood Case
Specification Brand New
Trademark Eltek
Origin Wuhan
HS Code 8504409190
Production Capacity 1000 Sets/Month
Product Description
Flatpack2 48V 3000W HE Rectifiers 241119.105 Eltek Rectifier Modules
The original HE rectifier
Since setting the new standard for rectifier efficiency, the Flatpack2 HE family is now available in a variety of voltages and power ratings, all with superior efficiency up to 96.5%.
With more than 4 billion in-field operating hours and a proven cumulative field MTBF of more than 1,9 million hours, Flatpack 2 HE is the only HE (High Efficiency) rectifier with a proven track record.
The line of systems available for Flatpack2 HE 48V rectifiers spans from 8kW 2U racks with complete distribution to multi-cabinet systems in multi MW installations.
APPLICATIONS
Microwave
Fiber Optics
Microwave
Broadband
Datacenters
Central Office
LTE / 4G / WIMAX
Telecom - Mobile / Wireless
Broadband Telecom - Fixed
Telephony Servers / Switches
Mobile Switching Center (Msc)
Radio Base Stations/ Cell Sites
Key Features
Proven Reliability
High Efficiency (HE)
Patented He Technology
Application Flexibility 2kw
Wide Temperature Range
Global Compliance (Ce, Ul)
Power Dense, Up To 33 W/Inch3
POWER UTILITIES
SCADA
POWER UTILITIES
CONTROL & PROTECTION
Specifications
Model48V / 3000W HE
Part number241119.105
INPUT DATA
Voltage (nominal)176 - 277 VAC
Voltage (range)85 - 305 VAC
Frequency45 - 66 Hz
Current (maximum) @ nominal input, full load19.2 ARMS
ProtectionFuse in both lines Varistor for transient protection
Disconnect above 305 VAC
OUPUT DATA
Voltage (default)53.5 VDC
Voltage (adjustable range)43.5 - 583) VDC
Power (maximum)3000 W
Power @ 85 VAC1380 W
Current (maximum) @ nominal input, full load62.5 A
Ripple, 30MHz bandwidth< 150 mVpp
Psophometric noise< 2 mVRMS
Static Voltage regulation±0.5% for 10 - 100% load
Dynamic Voltage regulation±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms
ProtectionFuse, Short circuit proof, High temperature protection, Hot plug-in inrush current limiting
Efficiency @ nominal input96 %
OTHER SPECIFICATIONS
Isolation3.0 kVAC - input to output, 1.5 kVAC - input to earth, 500 VDC - output to earth
Alarms: Red LED 'on'Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure
Warnings: Yellow LED 'on'Rectifier in power derate mode, Remote battery current limit activated, Input voltage out of range, flashing at overvoltage
Normal (module running): Green LED 'on'
Acoustic noise, full load @ Tambient = 25°C
full load @ Tambient = 40°C
< 40 dBA
< 58 dBA
MTBF (Telcordia SR-332 Issue I method III (a))>300 000 (@ Tambient : 25 °C)
Operating temperature-40 to +75°C (-40 to +167°F)4), humidity 5 - 95% RH non-condensing
Temperature de-rating>55°C4) (131°F), 2100W @ 75°C (167°F)4)
Storage temperature-40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight109 x 41.5 x 327mm (4.25 x 1.69 x 13") / 1.95 kg (4.3 lbs)
DESIGN STANDARDS
Electrical safetyEN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, UL 60950-1:2014, CSA C22.2 No.60950-1-07:2014, IEC 60950-1:2013
EMCEN 61000-6-1:2019, -6-2:2019, - 6-3:2007 + A1:2011, - 6-4:2019, EN 61000-3-2:2019 ETSI EN 300 386 V.2.1.1, Telcordia NEBS GR1089 CORE
MarineDNVGL-CG-03392)
EnvironmentETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3) EU 2015/863 (RoHS) & 2012/19/EU (WEEE)
Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised
power derating, maximum 1000W @ 230Vac 16 2/3 Hz
only valid for part number 241115.105M
57.6V for HW revision ≤ 5
from HW revision 6: shutdown at 95°C with de-rating to ~1000W